VFD (Variable frequency Drive)
description1
description2
Structural Topology
Product Features
Metal Film Capacitor Equipped with a 16-year life design, ensuring long-term reliability and reducing maintenance frequency.
Voltage Ride-Through High/low voltage ride-through capability to effectively avoid undesired frequency trips during grid fluctuations.
Single-Module Bypass Advanced bypass functionality to prevent complete system shutdown due to a single module failure.
Remote Monitoring Seamless WiFi / 4G connectivity enabling ease in service operations like trouble reporting and real-time analysis.
No Grid-Side Correction Required Satisfactory performance in harmonic mitigation; grid-side power factor > 0.95 (for loads ranging from 20% to 100% of rated capacity).
Vector Control Algorithm High-performance control logic, perfectly compatible with operating both asynchronous and synchronous motors.
Product Technical Parameters
| Project | 6kV Series | 10kV Series | |
|---|---|---|---|
| Input | Rated input voltage | AC 3PH 6kV | AC 3PH 10kV |
| Scope range of the fluctuation of voltage | -10% ~ +10% | ||
| Incoming frequency | 50/60Hz; ±5% | ||
| Input current harmonics | Complies with IEEE519-2014 and GB/T14549-93 standards | ||
| Output | Output voltage range | 0 - 6kV | 0 - 10kV |
| Output current range | Reference 2.4 - 4 Product Specifications and Dimensions | ||
| Output range | 0 - 5600kVA | 0 - 10000kVA | |
| Output power range | 0 - 4500kW | 0 - 8000kW | |
| Output frequency range | 0 - 120Hz (customizable above 120Hz) | ||
| Output current harmonics | ≤ 2% | ||
| Control Performance | Control method | V/F control, open-loop vector control, closed-loop vector control | |
| Processor Core (Navar) | DSP, FPGA, ARM | ||
| Human-computer interface | Touch screen | ||
| Speed ratio | 1:50 (V/F); 1:100 (open-loop vector); 1:200 (closed-loop vector) | ||
| Speed control accuracy | ±1% max speed (V/F); ±0.4% max speed (open-loop vector); ±0.2% max speed (closed-loop vector) | ||
| Torque response time | <200ms (open-loop vector); <100ms (closed-loop vector) | ||
| Overload protection / Accel time | 120% for 60s (every 5 mins), 180% immediate protection. Accel time: 0-3600s (customizable) | ||
| Input / Output | One-off input | 12-channel digital input | |
| Switching Output | 10 relay outputs (5 normally open, 5 normally open and closed), expandable to 12 | ||
| Real analogue input | 4 channels: A01, A12, A13 (0-10V / 4-20mA); A14 (-10V to 10V) | ||
| Analog Output | 3 channels: AO1, AO2, AO3 (0-10V / 4-20mA); 3 channels: AO4, AO5, AO6 (4-20mA) | ||
| Communication Mode | Supports Modbus protocol, standard RS485 interface, PROFIBUS, PROFINET, Ethernet, etc. | ||
| Defensive Function | System Protection | Overcurrent, overvoltage, undervoltage, motor overload, phase loss, overheating, thermostat failure, communication failure, access control, etc. | |
| Cell protection | Communication faults, undervoltage, overvoltage, overheating, input phase loss, VCE failure, bypass failure | ||
| General Data | Way to install | Cabinet installation | |
| Levels of protection | IP30 (customizable other protection ratings) | ||
| Noise level | ≤ 80dB | ||
| Entry / Exit method | Enter from the bottom, exit from the bottom (customizable upon request) | ||
| Cooling down method | Air blast cooling | ||
| Control source | AC 380V ±10% | ||
| MTBF | 50,000 hours | ||
| Operating environment temperature | -10℃ to +40℃ (Preheat required if < 0℃). Use at reduced capacity up to max 50℃. | ||
| Altitude (Above sea level) | Below 1000m. For every 100m increase above 1000m, reduce capacity by 1%. | ||
| Environment & Oscillation | Dust-free, sun-sheltered, non-flammable/corrosive gas, oil/water vapor free. Oscillation Amplitude: ≤ 0.59g | ||